Chapter 2
Preparation
2.3
Installation of dedicated CT, ZCT
The dedicated CT, ZCT is divided into the two types: split type and panel fixed (through) type.
[Common]
Measurement with single-phase 2-wire requires one dedicated CT, measurement with
single-phase 3-wire or 3-phase 3-wire requires two dedicated CTs, and measurement with
3-phase 4-wire requires three dedicated CTs.
The dedicated ZCT can be used for the measurement in single-phase 2-wire, single-phase
3-wire, 3-phase 3-wire, and 3-phase 4-wire.
Use of dedicated CTs in a circuit requires all the CTs to have the same standard.
The standard of the dedicated CTs to be used should match the settings of the dedicated
CT of Model KE1.
A dedicated CT has its polarity. Carry out wiring correctly between (K) and (L).
For terminal positions, refer to Page 2-16 and later.
Before making connections, confirm the directions of power supply side (K) and load side
(L). Wrong direction prevents correct measurements.
Securely close the terminal cover on the secondary side of dedicated CT.
Do not ground the dedicated CT. Doing so causes a failure.
Electric shocks may occur.
For the primary side wire to be clamped in CT, be sure to use a covered electric wire of 600
V or more in basic insulation.
When using a conductive object, such as bus bar, for clamping, ensure the basic insulation
at least by, e.g., covering with an insulator.
Avoid direct clamping in a line of 600 VAC or more.
[Split type]
Open the hook for the split/fixed type and clamp each phase. After clamping, securely
perform fitting until a clicking sound is heard.
[Panel fixing (through) type]
Securely fix the dedicated CT, ZCT to the panel, etc.
2-12