Over current alarm output
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
○
○
O: With alarm
X: Without alarm
•
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
•
Alarm judgment implements the OR operation in phases (when the value of a phase
exceeds the over current alarm threshold). In addition, release of an alarm implements the
AND operation (when the values of all phases are lower than over current alarm threshold
and current alarm hysteresis).
•
Over current alarm threshold
•
Over current alarm hysteresis
•
Over current alarm on-delay
* CTD8E (CT expansion) can perform the two-system measurement only when it is
connected to PMU2A (power two-system).
Under current alarm output
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
○
○
O: With alarm
X: Without alarm
•
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
•
Alarm judgment implements the OR operation in phases (when the value of a phase is
lower than the under current alarm threshold). In addition, release of an alarm implements
the AND operation (when the values of all phases exceed under current alarm threshold
and current alarm hysteresis).
•
Under current alarm threshold
•
Under current alarm hysteresis
•
Under current alarm on-delay
* CTD8E (CT expansion) can perform the two-system measurement only when it is
connected to PMU2A (power two-system).
Over voltage alarm output
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
○
○
O: With alarm
X: Without alarm
•
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
•
Alarm judgment implements the OR operation in phases (when the value of a phase
exceeds the over voltage alarm threshold). In addition, release of an alarm implements the
AND operation (when the values of all phases are lower than over voltage alarm threshold
and voltage alarm hysteresis).
•
Over voltage alarm threshold
•
Over voltage alarm hysteresis
•
Over voltage alarm on-delay
VSU1B
VAU1B
(Voltage sag)
(Voltage/current)
×
○
:
0.0 to 6000.0 A
:
0.0 to 1000.0 A
:
0.1 to 10.0 s
VSU1B
VAU1B
(Voltage sag)
(Voltage/current)
×
○
:
0.0 to 6000.0 A
:
0.0 to 1000.0 A
:
0.1 to 10.0 s
VSU1B
VAU1B
(Voltage sag)
(Voltage/current)
○
○
:
0.0 to 12100.0 V
:
0.0 to 2200.0 V
:
0.1 to 10.0 s
3.6
CTD8E
ZCT8E
(CT extension)
(ZCT extension)
○
×
(Initial value: 100.0 A)
(Initial value: 5.0 A)
(Initial value: 0.1 s)
CTD8E
ZCT8E
(CT extension)
(ZCT extension)
○
×
(Initial value: 10.0 A)
(Initial value: 5.0 A)
(Initial value: 0.1 s)
CTD8E
ZCT8E
(CT extension)
(ZCT extension)
×
×
(Initial value: 528.0 V)
(Initial value: 24.0 V)
(Initial value: 0.1 s)
Output function
3-23