Over Current Alarm Output; Under Current Alarm Output; Over Voltage Alarm Output - Omron KE1 User Manual

Smart power mersuring monitor
Table of Contents

Advertisement

 Over current alarm output
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
O: With alarm
X: Without alarm
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
Alarm judgment implements the OR operation in phases (when the value of a phase
exceeds the over current alarm threshold). In addition, release of an alarm implements the
AND operation (when the values of all phases are lower than over current alarm threshold
and current alarm hysteresis).
Over current alarm threshold
Over current alarm hysteresis
Over current alarm on-delay
* CTD8E (CT expansion) can perform the two-system measurement only when it is
connected to PMU2A (power two-system).
 Under current alarm output
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
O: With alarm
X: Without alarm
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
Alarm judgment implements the OR operation in phases (when the value of a phase is
lower than the under current alarm threshold). In addition, release of an alarm implements
the AND operation (when the values of all phases exceed under current alarm threshold
and current alarm hysteresis).
Under current alarm threshold
Under current alarm hysteresis
Under current alarm on-delay
* CTD8E (CT expansion) can perform the two-system measurement only when it is
connected to PMU2A (power two-system).
 Over voltage alarm output
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
O: With alarm
X: Without alarm
This function is available when output terminal function setting is selected as an alarm
after the setting of alarm parameter setting and alarm output setting.
Alarm judgment implements the OR operation in phases (when the value of a phase
exceeds the over voltage alarm threshold). In addition, release of an alarm implements the
AND operation (when the values of all phases are lower than over voltage alarm threshold
and voltage alarm hysteresis).
Over voltage alarm threshold
Over voltage alarm hysteresis
Over voltage alarm on-delay
VSU1B
VAU1B
(Voltage sag)
(Voltage/current)
×
:
0.0 to 6000.0 A
:
0.0 to 1000.0 A
:
0.1 to 10.0 s
VSU1B
VAU1B
(Voltage sag)
(Voltage/current)
×
:
0.0 to 6000.0 A
:
0.0 to 1000.0 A
:
0.1 to 10.0 s
VSU1B
VAU1B
(Voltage sag)
(Voltage/current)
:
0.0 to 12100.0 V
:
0.0 to 2200.0 V
:
0.1 to 10.0 s
3.6
CTD8E
ZCT8E
(CT extension)
(ZCT extension)
×
(Initial value: 100.0 A)
(Initial value: 5.0 A)
(Initial value: 0.1 s)
CTD8E
ZCT8E
(CT extension)
(ZCT extension)
×
(Initial value: 10.0 A)
(Initial value: 5.0 A)
(Initial value: 0.1 s)
CTD8E
ZCT8E
(CT extension)
(ZCT extension)
×
×
(Initial value: 528.0 V)
(Initial value: 24.0 V)
(Initial value: 0.1 s)
Output function
3-23