Omron KE1 User Manual page 102

Smart power mersuring monitor
Table of Contents

Advertisement

Appendix
【ZCT】
・Split core type
Model
Item
Primary standard current
Insulation resistance
Voltage withstood
Inner diameter
Working temperature/
humidity range
Storage temperature/
humidity range
・Through type
Model
Item
Model OTG-L21
Primary standard
50 A
current
Insulation
resistance
Voltage withstood
Inner diameter
21
dia.
Working
temperature/
humidity range
Storage
temperature/
humidity range
*1. Use the dedicated ZCT in a low-voltage circuit of 600 V or below
*2. When clamping at a conductive object, such as bus bar, ensure the basic insulation at least by
covering it with an insulator, etc.
A-8
Indoor split core type
Model OTG-CN52
Model OTG-CN77
200 A
400 A
Between charging portion and earth: 100 MΩ or more (500 DCV megger)
Between charging portion and earth: 2200 VAC 1 min.
52
dia.
77
-10 to + 60°C with 45 to 85% (without condensation)
-10 to + 60°C with 45 to 85% (without condensation)
Indoor through type
Model OTG-L30
Model OTG-L42
100 A
200 A
Between charging portion and earth: 100 MΩ or more (500 DCV megger)
Between charging portion and earth: AC2200V 1min
30
dia.
42
dia.
-10 to + 60°C with 45 to 85% (without condensation)
-10 to + 60°C with 45 to 85% (without condensation)
Model OTG-CN112
600 A
dia.
112
dia.
Model OTG-L68
Model OTG-L82
Model OTG-L156
400 A
600 A
68
dia.
82
dia.
Outdoor split core type
Model OTG-CN36W
150 A
36
dia.
Outdoor
through type
Model OTG-LA30W
1000 A
100 A
156
dia.
30
dia.