Chapter 2
Preparation
2.5
Wiring
■ Requests for wiring
Do not change the terminal screws, but use existing screws.
To prevent being affected by noise, wiring of signal line should be different from that of power
line.
Cable to be used for wiring terminals excepting CT should be twist pair AWG25 (whose
cross-sectional area is 0.205 mm2) to AWG12 (whose cross-sectional area is 3.309 mm2).
For circuits in use, select appropriate cables.
When connecting dedicated CT, use the cable for dedicated CT (Model KM20-CTF-CB3: 3
m).
When doing so, connect the shrinkable tube side to the dedicated CT.
For RS-485 connection, the total cable length is up to 500 m.
Do not ground the dedicated CT or RS-485 signal line. Doing so causes a failure.
For the terminal section, carry out wiring by using a solderless terminal.
Use wiring materials and crimp tools that are suitable for the solderless terminal.
Tighten a terminal screw to the torque of 0.69 to 0.88 Nm.
For a solderless terminal, use the M3.5 terminal whose shape is as follows.
■ Wiring
● Power voltage
PGR1C
(Electric
power/leakage)
power/voltage sag)
○
Connect between terminals [1] and [2].
The specifications are as follows.
Power voltage
AC100~240 V (50/60 Hz)
2-30