Alarm Output; Alarm History; Time Chart Of Alarm Output Function - Omron KE1 User Manual

Smart power mersuring monitor
Table of Contents

Advertisement

 Alarm output
Alarm output upper/lower limit threshold, alarm output hysteresis, alarm output on-delay
can be set.
Setting hysteresis can prevent frequently turning ON/OFF an alarm even when a
measurement value varies near the alarm output judgment value.
On-delay is a function that keeps the output OFF for the specified hours and minutes. Set
an optimum value.
Setting the upper limit threshold of each alarm to the maximum value turns the upper limit
alarm function OFF, while setting the lower limit threshold to the minimum value turns the
lower alarm function OFF. The setting should be made to use only either upper limit alarm
or lower limit alarm.
* Do not use the alarm output function in cases related to safety, e.g., machine control, etc.,
because the function is assumed to detect errors and call attention by sounding a buzzer
or lighting a lamp.
 Alarm history
Histories of alarms generated in the past can be confirmed via communication.
Histories of only 20 alarms generated in the past can be read. If the number of alarms
generated exceeds 20, histories are deleted from the oldest one.
Alarm type, and time of alarm generation: The circuit in which an alarm was generated, and
Alarm release time:
 Time chart of alarm output function
With on-delay setting, without hysteresis setting
Upper limit threshold
上限閾値
Lower limit threshold
下限閾値
Upper limit alarm judgment
上限警報判定
Lower limit alarm judgment
下限警報判定
On-delay judgment
オンディレー判定
Upper limit alarm output
上限警報出力
Lower limit alarm output
下限警報出力
*1. Turn the alarm output OFF if the state remains OFF continuously in on-delay hour/minute and
alarm judgment.
the time of generation are saved at first.
Saved when all circuits to be judged have been
alarm-released.
*1
*1
3.6
Output function
3-21