Model
Item
Leakage
Operation setting range
monitoring
Operation characteristics
Operating time setting
range
Operation time
characteristics
Recovery condition
Voltage sag
Voltage sag detection
monitoring
voltage setting range
Tolerance of detected
voltage
Duration setting range
Accuracy of relay output
operating time
Open-phase
Open-phase detection
monitoring
condition
Operation characteristics
Operation time
Operation time
characteristics
Recovery condition
Reverse phase
Operation time
monitor
Operation time
characteristics
 Accessories
 Connection connector (excepting measurement master)
 Instruction Manual (Japanese, English, Korean)
A-6
PGR1C
PVS1C
(Electric power
(Electric power
/leakage)
/voltage sag)
30 to 1,000 mA
±5% rdg
(30 to 200 mA)
±1% FS
(200 to 1,000 mA)
0.1 to 20.0 s
±0.2 s
95% of operate
value
0.0 to 480.0 V
±2.5% FS
Backup unavailable: 0.02 to 0.2 s
Backup available: 0.02 to 1.00 s
±5 ms
In 3-phase voltage, (Max. difference between each phase voltage and average
voltage/average voltage) x 100 ・ 85%
±1.0% FS ±1 digit
* However, voltage between Vtr shall be ±2.0% FS ±1 digit under the same
condition.
0.1 s
±0.2 s
Unbalance factor of less than 13%
0.1s
±0.2s
VSU1B
VAU1B
(Voltage sag)
(Voltage/current)
CTD8E
ZCT8E
(CT
(ZCT
extension)
extension)
30 to 1,000 mA
±5% rdg
(30 to 200 mA)
±1% FS
(200 to 1,000 mA)
0.1 to 20.0 s
±0.2 s
95% of operate
value

Advertisement