Configuration Menu; Calibration Menu - Det-Tronics X9800 Addendum

Hart communication with the ir flame detector
Hide thumbs Also See for X9800:
Table of Contents

Advertisement

CONFIGURATION MENU

X9800 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
1) Cons IR o i Fails
2) Time Delay

CALIBRATION MENU

X9800 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
1) Loop test
2) D/A trim
3) Calibrate o i
2.2
Device Setup Menu
1) Configuration Menu
2) Calibration Menu
3) Write Protect
4) HART Setup
5) Real Time Clock
Allowable number of consecutive IR o i failures to produce a fault. Factory
set to three (minutes). This is the time between fault occurrence and
annunciation.
Time Delay before alarm is indicated (0 to 15 seconds). Factory default is
zero seconds.
Important: In addition to lengthening the time period between the outbreak
of a fire and the fire alarm, a time delay can also affect sensitivity. Consult the
factory for guidance before setting a time delay over five seconds.
Note: FM Approval covers the detector's performance with zero time delay
only.
Device Setup Menu
1) Configuration Menu
2) Calibration Menu
3) Write Protect
4) HART Setup
5) Real Time Clock
This test allows the operator to manually set the analog signal output at 1, 2,
3, or between 4 and 20 mA in increments of 2 (4, 6, 8, etc.). When the loop
test is completed, ensure that the current loop is returned to automatic operation.
This function allows adjustment of the 0–20 mA span factor.
Trim in increments of 0.1 mA resolution only.
This procedure calibrates the o i test signal for the IR sensor.
1. Bypass/disable all Alarm outputs connected to the detector.
2.
Thoroughly clean the sensor and o i reflector for the IR sensor.
Check the o i source openings for contaminants and clean as
needed.
3.
Cover the detector with the provided cover.
4.
Initiate o i Calibration. The detector performs the calibration
automatically and notifies the operator upon completion. The
procedure takes approximately two minutes.
5.
Upon completion of o i calibration, remove the cover and return all
alarm outputs to service.
Configuration Menu
1) Cons IR Oi Fails
2) Time Delay
Calibration Menu
1) Loop test
2) D/A trim
3) Calibrate Oi
NOTE
16
95-8637