Write Protect - Det-Tronics X9800 Addendum

Hart communication with the ir flame detector
Hide thumbs Also See for X9800:
Table of Contents

Advertisement

WRITE PROTECT

This function enables the operator to enable/disable password and write protection capability, as well
as to enter or change a password. The device is provided from the factory with Write Protect off. With
Write Protect on, the use of a password is required to enable writing to the device.
X9800 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
1) Set Password
2) Set Write Protect
3) Write protect (Y/N) This indicates whether or not Write Protect is enabled.
2.2
Device Setup Menu
1) Configuration Menu
2) Calibration Menu
3) Write Protect
4) HART Setup
5) Real Time Clock
The password is used to validate the command to enable or disable writes
in the device. (The factory default password is: 1*******. Once the password
has been changed, the default password is no longer valid.)
To change the password:
1. Select "Set Password" and enter the password. Hit "Send."
2. If enabled, disable Write Protect. Hit "Send."
3. Select "Set Password" and enter a new password. Do not hit "Send" yet.
4. From within the "Set Write Protect" menu, select "Change Password."
Hit "Send."
Always record the new password. If the password is forgotten, the device
must be returned to the factory for re-programming.
With Write Protect enabled, variables cannot be written to the device and
commands that cause actions to be performed in the device cannot occur.
Write Protect
1) Set Password
2) Set Write Protect
3) Write protect (Y/N)
CAUTION
17
95-8637