The X2200 with pulse/relay output is designed for use OUTPUTS in controller based systems. In addition to use in new Relays systems, it can serve as a direct field replacement The detector is furnished with fire and fault relays.
ATTENTION the location marked “MAG OI” on the outside of the The X2200 contains a source tube that is filled detector (see Figure 2). This action causes the detector with a gas mixture containing Krypton 85 (Kr to immediately send pulses to the controller.
To reset the controller status and alarms, place the selected sensitivity level. keylock switch in RESET. Return the keylock switch to NORMAL when testing is complete. The UV detector in the X2200 can be programmed for: – Arc Rejection The Man...
Artificial Lighting It is important to keep the detector viewing windows as The X2200 should not be located within 3 feet, 0.9 m free of contaminants as possible in order to maintain of artificial lights. Excess heating of the detector could maximum sensitivity.
IMPORTANT SAFETY NOTES Table 2—UV Absorbing Gases and Vapors The following is a partial list of compounds that exhibit WARNING significant UV absorption characteristics. These are also usually hazardous vapors. While generally of little Do not open the detector assembly in a hazardous consequence in small amounts, these gases can restrict area when power is applied.
Refer to Figure 2 and ensure that the plate will be unobstructed view of the area to be protected. oriented as shown when the X2200 is mounted and The following factors should also be taken into sighted. This will ensure proper operation of the...
IMPORTANT cable is recommended. Wires should be stripped Devices certified for hazardous locations shall be 3/8 inch (9 mm). In some cases where the X2200 is installed in accordance with EN/IECEx 60079-14 replacing existing pulse output detectors, the wiring and NEC 505 and power supplies may not be adequate.
Page 10
CAUTION IMPORTANT Installation of the detector and wiring should be If installing an X2200 in place of an existing performed only by qualified personnel. detector, be sure to move the “A” Lead (detector power) at the controller from the +290 Vdc source Detector Installation to the +24 Vdc source.
Page 11
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO TERMINAL J1-3 (290 VDC). R7404 CONTROLLER ZONE OUTPUT 1 10 TO 38 VDC – – ZONE OUTPUT 2 X2200 (A) +290 VDC ZONE OUTPUT 3 B - INPUT 1 ZONE OUTPUT 4...
Page 12
NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 2/12 DC+ ("A" LEAD) SIGNAL ("B" LEAD) NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). ("D" LEAD) GROUND FAULT PROTECTED SYSTEMS Figure 7—A Typical System, X2200 Detectors Wired to R7404 Star Logic Controller 95-8552...
Page 13
DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) SIGNAL ("B" LEAD) NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). ("D" LEAD) GROUND FAULT PROTECTED SYSTEMS Figure 8—A Typical System, X2200 Detectors Wired to R7494 Controller 95-8552...
Page 14
DC– ("C" LEAD) 2/12 DC+ ("A" LEAD) SIGNAL ("B" LEAD) NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE 0.5 REQUIREMENTS (SIGNALING LINES A AND C). ("D" LEAD) GROUND FAULT PROTECTED SYSTEMS Figure 9—A Typical System, X2200 Detectors Wired to R7495 Controller 95-8552...
Page 15
NOTE: DO NOT CONNECT THE X2200 "A" LEAD (#2/12) TO TERMINAL J2-34 (290 VDC). R7405 CONTROLLER (NOT FM APPROVED) +24 VDC GROUND – X2200 DETECTOR 1 X2200 J2-44 J2-36 DETECTOR 2 X2200 +290 VDC J2-45 J2-37 DETECTOR 3 X2200 J2-46...
Page 16
X2200 DETECTOR FIRE ALARM PANEL PULSE OUT SPARE SPARE COM FIRE 2 N.O. FIRE 2 N.C. FIRE 2 END OF LINE DEVICE 4 ALARM COM FAULT 1 RS-485 A N.O. FAULT 1 RS-485 B + Vin MAN O i 24 VDC –...
STARTUP PROCEDURE EOL RESISTORS To ensure that the insulating material of the wiring terminal When installation of the equipment is complete, apply block will not be affected by the heat generated by EOL power and allow 20 to 30 minutes for the detector’s resistors, observe the following guidelines when installing heated optics to reach equilibrium.
TROUBLESHOOTING 3. Press the SELECT button until the desired zone is displayed on the ZONE indicator on the controller front panel. WARNING The sensor module (“front” half of the detector) 4. Press and hold the TEST button. The DETECTOR/ contains no user serviceable components and ZONE display indicates the counts per second (cps) should never be tampered with.
IMPORTANT To maintain maximum sensitivity and false alarm When used in extreme environments, the reflective resistance, the viewing windows of the X2200 must be surface of the detector plate may eventually kept relatively clean. Refer to the following procedure for...
SPECIFICATIONS PERIODIC CHECKOUT PROCEDURE A checkout of the system using the Mag or Man OPERATING VOLTAGE— feature should be performed on a regularly scheduled 24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). basis to ensure that the system is operating properly. To Maximum ripple is 2 volts peak-to-peak.
Page 21
CONE OF VISION— DIMENSIONS— The detector has a 90° cone of vision (horizontal) with See Figure 16. the highest sensitivity lying along the central axis. WIRING— See Figure 15. Field wiring screw terminals are UL/CSA rated for up to 14 AWG wire, and are DIN/VDE rated for 2.5 mm wire.
Pulse Output Prior to returning devices, contact the nearest local Detector Electronics office so that a Return Material Refer to the X2200 Model Matrix for details. Authorization (RMA) number can be assigned. A Q9033 mount is required: written statement describing the malfunction must Q9033A for aluminum detectors only.
T6 (Tamb –40°C to +60°C) T5 (Tamb –40°C to +75°C) ZONE 21, AEx tb IIIC T80°C Tamb –40°C to +75°C IP66/IP67 The following accessories are FM approved for use with the X2200 Flame Detector: Part Number Description 102740-002 Magnet 007739-001...
Page 25
FM Approval and Performance Report – Continued RESPONSE CHARACTERISTICS Very High Sensitivity Distance Typical Response Time Fuel Size Mode feet (m) (seconds) n-Heptane 1 x 1 foot 85 (25.9) Low Arc Methane 32 inch plume 100 (30.5) Low Arc High Sensitivity Distance Typical Response Time Fuel...
Page 26
FM Approval and Performance Report – Continued FIELD OF VIEW Very High Sensitivity Typical Typical Distance Horizontal Vertical Fuel Size Response Time Response Mode feet (m) (degrees) (degrees) (seconds) (seconds) 42.5 n-Heptane 1 x 1 foot Low Arc (13) –45 –30 Methane 32 inch plume...
Page 27
FM Approval and Performance Report – Continued MODEL X2200M The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with unusual chemistry such as black powder. Consult factory for usage recommendations. X2200M RESPONSE CHARACTERISTICS High Sensitivity Distance...
APPENDIX B CSA APPROVAL DIVISION CLASSIFICATION: Ultraviolet Flame Detector/Controller X2200 series, rated 18-30 Vdc, 2.5 Watts to 7.6 Watts. Relay contacts rated 5 Amps @ 30 Vdc. CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);...
2.5 watts. • The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical damage. • See the "Maintenance" section of this manual for guidance on minimizing risk from electrostatic discharge.
Page 30
IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable blanking elements. NOTE For ATEX installations, the X2200 Flame Detector housing must be electrically connected to earth ground. The following accessories are ATEX approved for use with the X2200 Flame Detector: Part Number...
2.5 watts. • The Ultraviolet (UV) flame detector type X2200 is to be installed in places where there is a low risk of mechanical damage. • See the "Maintenance" section of this manual for guidance on minimizing risk from electrostatic discharge.