Hart Command Menu; Device Setup Menu - Det-Tronics X9800 Addendum

Hart communication with the ir flame detector
Hide thumbs Also See for X9800:
Table of Contents

Advertisement

HART COMMAND MENU

The HART Command Menu allows the operator to perform diagnostic and service functions as follows:
X9800 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu

5) Device Setup Menu

1) Self test
Internal tests are performed and any detected problems are reported in "Status
Info." If successful, indication will be "No Device Info on Self Test."
2) Master Reset
This function re-initializes the microprocessor, resets the operating software, and
initiates a hardware reset for both the sensor and the HART interface. Latched relays
are reset.
3) Loop test
This test allows the operator to manually set the analog signal output at 1, 2, 3, or
between 4 and 20 mA in increments of 2 (4, 6, 8, etc.). When the loop test is completed,
ensure that the current loop is returned to automatic operation.
DEVICE SETUP MENU
This menu allows various setup, configuration, and calibration functions. When Write Protect is off, these
menus allow the operator to reconfigure or write new variables to the device.
X9800 Root Menu
1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu
1) Configuration Menu
2) Calibration Menu
3) Write Protect
4) HART Setup
5) Real Time Clock
Refer to the appropriate sub-menus for details.
2.2
Command Menu
1) Start Passive Oi
2) Start Active Oi
3) Clear Oi Fault
4) Reset Latches
5) Master Reset
6) Clear Data Log
7) HART Command Menu
Device Setup Menu
1) Configuration Menu
2) Calibration Menu
3) Write Protect
4) HART Setup
5) Real Time Clock
15
HART Command Menu
1) Self test
2) Master Reset
3) Loop test
95-8637