DESCRIPTION normal condition and notifies personnel of fire alarm or fault conditions. The X2200, X2200G, and X2200M UV Flame Detectors meet the most stringent requirements worldwide The detector housing is available in copper-free aluminum with advanced detection capabilities and immunity or stainless steel, with Type 4X and IP66/IP67 rating.
ATTENTION of the detector to generate or maintain an alarm output, The X2200, and X2200M contain a source tube i.e., loss of operating power. that is filled with a gas mixture containing Krypton 85 (Kr ), a radioactive material.
Mag or Man switch. In this case, the detector's optics should be cleaned The UV detector in the X2200, X2200G, and X2200M and the tests should be repeated. See the "Cleaning can be programmed for: Procedure"...
See Appendix A for third-party approved fire test results. Glass and Plexiglas windows significantly attenuate UV Additional fire test results are available from Det-Tronics. radiation and must not be located between the detector and a potential flame source. If the window cannot be...
IMPORTANT SAFETY NOTES Table 3—UV Absorbing Gases and Vapors The following is a partial list of compounds that exhibit WARNING significant UV absorption characteristics. These are also usually hazardous vapors. While generally of little Do not open the detector assembly in a hazardous consequence in small amounts, these gases can restrict area when power is applied.
• If possible, fire tests can be conducted to verify O-rings is a silicone-free grease (p/n 005003- correct detector positioning and coverage. 001) available from Det-Tronics. Under no • For ATEX/IECEx installations, the detector housing circumstances should a lubricant containing must be electrically connected to earth ground.
PROTECTION AGAINST MOISTURE DAMAGE NOTE R e f e r t o “ Po w e r C o n s u m p t i o n” i n t h e It is important to take proper precautions during “Specifications”...
Page 10
Model) Relay and 0-20 mA Output Models To ensure that the insulating material of the wiring Follow the instructions below to install the X2200, terminal block will not be affected by the heat generated X2200G, or X2200M: by resistors, observe the following guidelines when installing the resistors.
Page 11
X2200 DETECTOR FIRE ALARM PANEL mA – mA + SPARE SHIELD mA + REF mA – REF SPARE COM FIRE 2 COM AUX COM FIRE NO FIRE 2 NO AUX NO FIRE DEVICE 4 NC FIRE 2 NC AUX NC FIRE...
Page 12
SHIELD X2200 DETECTOR FIRE ALARM PANEL mA + mA – SPARE mA + REF mA – REF SPARE COM FIRE 2 ALARM COM AUX COM FIRE DEVICE 4 NO FIRE 2 NO AUX ALARM NO FIRE NC FIRE 2 NC FIRE...
Page 13
X2200 DETECTOR X2200 DETECTOR mA + mA – 600 Ω MAX mA + 600 Ω MAX mA – AT 24 VDC AT 24 VDC mA – REF mA + REF – – 24 VDC 24 VDC – – MAN O i...
Page 14
EQP Model 5. Check all field wiring to be sure that the proper connections have been made. 1. Connect external wires to the appropriate terminals inside the terminal compartment, shown in Figure 14. 6. Replace and securely tighten all covers before See Figure 15 for terminal identification.
ADDRESS SWITCHES SENSOR MODULE REMOVED FROM HOUSING A2191 Figure 17—Location of Address Switches SETTING DEVICE NETWORK ADDRESSES The address number is binary encoded with each switch (EQ and EQP Models Only) having a specific binary value with switch 1 being the LSB (Least Significant Bit), see Figure 18.
STARTUP PROCEDURE 5. The use of the Enhanced Flame Inspector cable and software from Det-Tronics can be considered to When installation of the equipment is complete, perform determine the nature of the fault condition. Refer to the the “Fire Alarm Test” below.
Refer to surface of the detector reflector plate may Table 1 in the X2200/X2200G Safety manual, number eventually deteriorate, resulting in reoccurring 95-8672, for frequency of proof tests. To test the system,...
FEATURES SPECIFICATIONS • Responds to a fire in the presence of modulated OPERATING VOLTAGE— blackbody radiation (i.e., heaters, ovens, turbines) 24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). without false alarm Maximum ripple is 2 volts peak-to-peak. • High speed capability POWER CONSUMPTION—...
Page 20
WIRING— 100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF Field wiring screw terminals are UL/CSA rated for up to INCIDENCE DECREASES. 14 AWG wire, and are DIN/VDE rated for 2.5 mm wire.
Prior to returning devices, contact the nearest local X2200, X2200G, or X2200M UV Flame Detector Detector Electronics office so that a Return Material Refer to the X2200 Series Model Matrix for details. Authorization (RMA) number can be assigned. A Q9033 Mounting Arm is required: written statement describing the malfunction must –...
T6 (Tamb –40°C to +60°C) T5 (Tamb –40°C to +75°C) Zone 21, AEx tb IIIC T80°C Tamb –40°C to +75°C IP66/IP67 The following accessories are FM approved for use with the X2200, X2200G and X2200M Flame Detectors: Part Number Description 102740-002 Magnet...
Page 24
Standard Methane 32 inch plume 55 (16.8) Hi Arc *Add 2 seconds for EQP model. X2200 and X2200G RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES Very High Sensitivity (Standard Mode) Average Distance Distance False Alarm Source Fire Source...
Page 25
FM Approval and Performance Report – Continued X2200 and X2200G Field of View Very High Sensitivity Average Average Distance Horizontal Vertical Fuel Size Response Time Response Mode feet (m) (degrees) (degrees) (seconds)* (seconds)* 42.5 n-Heptane 1 x 1 foot Low Arc (13) –45...
Page 26
FM Approval and Performance Report – Continued MODEL X2200M The X2200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with unusual chemistry such as black powder. Consult factory for usage recommendations. X2200M RESPONSE CHARACTERISTICS High Sensitivity Distance...
– Explosive atmospheres. Part 7: Equipment protection by increased safety "e" CAN/CSA-C22.2 No. 60079-31: 2012 – Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure "t" The following accessories are CSA approved for use with the X2200, X2200G, and X2200M Flame Detectors: Part Number Description...
APPENDIX C ATEX APPROVAL EC-TYPE EXAMINATION CERTIFICATE DEMKO 02 ATEX 132195X Increased Safety Model Flameproof Model II 2 G II 2 G 0539 0539 ® II 2 D ® II 2 D APPROVED APPROVED Ex db eb IIC T6...T5 Gb Ex db IIC T6...T5 Gb Ex tb IIIC T85°C Db Ex tb IIIC T85°C Db...
APPENDIX D IECEx APPROVAL CERTIFICATE OF CONFORMITY IECEx ULD 06.0018X Ex db eb IIC T6...T5 Gb Ex db IIC T6...T5 Gb Ex tb IIIC T85°C Db Ex tb IIIC T85°C Db T6 (Tamb = –50°C to +60°C) T6 (Tamb = –55°C to +60°C) T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C) IP66/IP67.
INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM The installation of the X2200 and X2200G flame detectors meet the directional dependence requirements of EN 54- 10, Clause 5.4 for any β angle when the α angle does not exceed ±30° (total field of view = 60°).
Certified SIL 2 Capable. Ex db eb IIC T6...T5 Applies to specific models – refer to the SIL 2 Certified Ex tb IIIC T80°C X2200/X2200G Safety Manual (95-8672) for details. T6 (Tamb -50°C TO +60°C) T5 (Tamb -50°C TO +75°C) IP66/IP67 - OR - RUSSIA &...
APPENDIX G DECLARATION OF CONFORMITY EU Declaration of Conformity Model X2200 Series (Ultraviolet Flame Detector) The object of the declaration described above is in conformity with the relevant Union harmonisation legislation: ATEX Directive: 2014/34/EU Certificate No.: DEMKO 01 ATEX 132195X...