Signals; Status Signals Via Output Contacts (Digital Outputs); Assignment Of Outputs; Encoding Of Outputs - AUMA SAEx 07.2 Operation Instructions Manual

Multi-turn actuators with actuator controls aumatic acexc 01.2 non-intrusive
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Signals

8.
Signals
8.1.

Status signals via output contacts (digital outputs)

Characteristics
8.1.1.

Assignment of outputs

8.1.2.

Encoding of outputs

8.2.

Analogue signals

Valve position
Torque feedback
44
SAEx 07.2
SAEx 16.2 / SAREx 07.2
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
The output contacts (outputs DOUT 1
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Default values:
Signal DOUT 1 = Fault
Signal DOUT 2 = End position CLOSED
Signal DOUT 3 = End position OPEN
Signal DOUT 4 = Selector sw. REMOTE
Signal DOUT 5 = Torque fault CLOSE
Signal DOUT 6 = Torque fault OPEN
Signal DOUT 7 = End position CLOSED
Signal DOUT 8 = End position OPEN
Signal DOUT 9 = Selector sw. REMOTE
Signal DOUT 10 = Torque fault CLOSE
Signal DOUT 11 = Torque fault OPEN
Signal DOUT 12 = Fault
The output signals DOUT 1
High active = output contact closed = signal active
Low active = output contact open = signal active
Required user level: Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values for DOUT 1
Signal: E2 = 0/4
20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT1 (position)
Signal: E6 = 0/4
20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT2 (torque)
For further information on this topic, please refer to Manual (Operation and setting).
SAREx 16.2 Control unit: electronic (MWG)
12) can be assigned to various signals.
12 can be set either to high active or low active.
12: High active
ACExC 01.2 Non-Intrusive

Advertisement

Table of Contents
loading

This manual is also suitable for:

Saex 16.2Sarex 07.2Sarex 16.2