Design
Observe prior to connec-
tion
5.4.2.

Parking frame

Application
SAREx 16.2 Control unit: electronic (MWG)
Figure 20: Design principle with wall bracket
[1]
Wall bracket
[2]
Connecting cables
[3]
Electrical connection of wall bracket (XM)
[4]
Electrical connection of actuator (XA)
[5]
Electrical connection of controls (XK)
Permissible length of connecting cables: max. 100 m.
Permissible length of connecting cables for later separation of actuator and
controls: max. 10 m.
We recommend: AUMA cable sets LSW21-KES or LSW22-KP.
If the AUMA cable set is not used:
-
Use suitable flexible and screened connecting cables.
-
Use separate CAN bus cable of 120 Ohm character impedance for MWG
(e.g. UNITRONIC BUS-FD P CAN UL/CSA - 2 x 2 x 0.5 mm², manufacturer:
Lapp).
-
Data cable connection: XM2-XA2 = CAN L, XM3-XA3 = CAN H.
-
Voltage supply MWG: XM6-XA6 = GND, XM7-XA7 = + 24 V DC (refer to
wiring diagram).
When using connecting cables, e.g. of the heater, requiring direct wiring from
the actuator to the XK customer connector (XA-XM-XK, refer to wiring diagram),
these connecting cables must be subject to an insulation test in compliance
with EN 50178. Connecting cables for MWG do not belong to this group. They
may not be subject to an insulation test.
Parking frame for safe storage of a disconnected plug.
For protection against touching the bare contacts and against environmental
influences.
Electrical connection
customer connector
27