Status Indications According To Namur Recommendation - AUMA SAEx 07.2 Operation Instructions Manual

Multi-turn actuators with actuator controls aumatic acexc 01.2 non-intrusive
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2 / SAREx 07.2
ACExC 01.2 Non-Intrusive
7.2.3.

Status indications according to NAMUR recommendation

SAREx 16.2 Control unit: electronic (MWG)
Figure 47: Fault
For further information, please also refer to <Corrective action>.
These indications are available, if the parameter Diagnostic classific. M0539 is set
to NAMUR.
Out of Specification (S0008)
The S0008 indication shows out of specification indications according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows S0008:
the number of indications occurred
a blinking triangle with question mark after approx. 3 seconds
Figure 48: Out of specification
For further information, please also refer to <Corrective action>.
Function check (S0009)
The S0009 indication shows function check indications according to NAMUR
recommendation NE 107.
If an indication has occurred via the function check, the display shows S0009:
the number of indications occurred
a blinking triangle with a spanner after approx. 3 seconds
Figure 49: Function check
For further information, please also refer to <Corrective action>.
Maintenance required (S0010)
The S0010 indication shows maintenance indications according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows S0010:
the number of indications occurred
a blinking square with an oil can after approx. 3 seconds