Extension Unit Exu-Sa - Assa Abloy SW200 Installation And Service Manual

Hide thumbs Also See for SW200:
Table of Contents

Advertisement

12.1.5

Extension unit EXU-SA

This extension unit has inputs for door mounted sensors, which can give presence impulse on approach side
and/or presence detection on swing path side. Relay output for error indication or door indication is also integ-
rated. When the jumper for the relay is set to 'Open door indication', its activation will follow the Blanking LED.
Functions
Monitoring of presence detection/DMPS.SS
Monitoring of presence impulse/DMPS.NS
Blanking LED
2)
Door mounted sensors
DMPS:
Relay 1: Presence im-
pulse (NC)
Relay 2: Presence detec-
tion (NC)
MIN
Closed door
indication
MIN
QTST = Sensor monitoring and reference for KILL (NC)
PDET = Presence detection (NC)
PIMP = Presence impulse (NC)
1)
If not used strap to "Ground".
2)
Remove strapping from terminals 2 and/or 3.
1009728-en-9.0
No monitoring (both jumpers on)
Monitoring of presence detection and presence impulse
NO
COM
NC
(+) 24 VDC
24 V DC
QTST
PDET
PIMP
GND
(-) 0 VDC Ground
Remove strapping when connecting to terminals 2
and/or 3
Blanking potentiometer
(Adjust the potentiometer to avoid presence detection sensor to detect the wall.
Range 55 degrees - fully open / Max.)
Opened / closed door indication
MAX
Open door
MAX
indication
1)
1)
Issue 2021-02-24
External error indication/KILL OUT/Lock
Opened/closed door indication
Relay output ("External error, KILL OUT, Lock indication" or
"Open/closed door indication", see above) 24 V, 1 A
Note! To make the dry relay output follow the electric lock output,
see group parameters 14, 15 and 16 plus pin jumper above.
Not to be used.
Ground
Blanking
Blanking
12 Electrical connection
MAX
55°
55

Advertisement

Table of Contents
loading

Table of Contents