Note: For 14/20RESA and 20RESC three-phase
models, leads 1--12 are the generator output
leads. Leads V7, V8, V9, 55, and 66 are the
controller sensing and supply leads. Refer to the
schematic in Figure 6-6 when performing the
following steps.
Figure 6-6 Three-Phase Alternator Stator Leads
(14/20RESA, 20RESC)
6. Contact the ohmmeter leads and readjust the
ohmmeter to read zero ohms.
7. Check the cold resistance of the stator windings by
connecting the meter leads to stator lead pairs
shown in Figure 6-7 (single-phase) or Figure 6-8
(14/20RESA and 20RESC three-phase).
Section 1.6, Alternator Specifications, for stator
winding resistances.
provide accurate readings below 1 ohm. Low
resistance readings (continuity) and no evidence of
shorted windings (heat discoloration) indicate a
stator in good condition.
Leads
1 and 2
1 and 11
2 and 11
3 and 4
3 and 44
4 and 44
55 and 66
1 and 3, 4, 44, 55, or 66
2 and 3, 4, 44, 55, or 66
3 and 1, 2, 11, 55, or 66
4 and 1, 2, 11, 55, or 66
Any stator lead and ground on stator
housing or frame laminations
Figure 6-7 Continuity Test Results on a Good
Stator, Single-Phase
TP-6805 8/15
tp6198
See
Most ohmmeters do not
Continuity
Yes
No
Leads
1 and 4
2 and 5
3 and 6
7 and 10
8 and 11
9 and 12
55 and 66
1 and 2, 3, 7, 8, or 9
1 and 55
Any stator lead and ground
Figure 6-8 Continuity Test Results on a Good
Stator, Three-Phase (14/20RESA,
20RESC)
8. If the resistance test proves inconclusive, use a
megohmmeter to test the stator as described in the
next step.
Note: Because
ohmmeter
resistance
readings. Take readings of the rotor and
stator at room temperature.
Note: Make sure that all stator leads are
disconnected
megohmmeter test.
9. Use a megohmmeter to determine whether the
stator is shorted to ground.
a. Apply 500 volts DC to any stator lead and the
stator frame. Perform the megohmmeter test
following the instructions of the megohmmeter
manufacturer.
b. Repeat the test on the other stator leads until
each coil is tested.
Note: A reading of approximately 500 kOhms
(1/2 megohm) and higher indicates a
good stator.
c. Repair or replace the stator if any reading is
less than approximately 500 kOhms. A reading
of less than 500 kOhms indicates deterioration
of the winding insulation and possible current
flow to ground.
Section 6 Component Testing and Adjustment
Continuity
Yes
No
accuracy
varies,
readings
are
approximate
before
running
the
97