21. Remove the alternator support bracket from the
alternator shell. See Figure 7-22.
1. Alternator support bracket
Figure 7-22 Alternator Support Bracket (RESA
shown)
22. Remove the cable tie that attaches the brush leads
to the end bracket. See Figure 7-23.
23. Check the brushes. See Figure 7-23.
Note: The
brushes
captured in the brush holder.
a. Remove the brush holder from the end bracket
by removing two mounting screws.
b. Inspect the brushes. Replace brushes if they
show uneven wear or when they are worn to
half of their original size. See Section 6.6,
Brushes.
TP-6805 8/15
1
TP-6735
are
spring-loaded
and
3
2
4
GM62996
5
1
1
1. Brush(es)
2. Brush holder
3. Slip rings
Figure 7-23 Brush Assembly
Section 7 Disassembly/Reassembly
4
1
GM80980
2
GM80982
Spring Not
Shown
Length New
19.0 mm
(0.75 in.)
GM80981
4. Shim
5. Spring
135