7.3.4
Reinstall Enclosure, 20RESB and
20RESD
21. Reinstall the alternator air inlet duct. Orient the
duct as shown in Figure 7-38.
22. Install the exhaust duct. See Figure 7-38.
23. Reconnect the following alternator wiring inside the
controller junction box. See the wiring diagrams in
Section 8.
a. Reconnect lead 55 to the mini-breaker on the
controller.
b. Reconnect P2 to the controller.
c. Reconnect leads 2 and 3 to neutral stud L0.
d. Reconnect leads 1 and 4 to the circuit breaker.
e. Reconnect any other controller connections
that were removed during disassembly.
Exhaust and
Alternator Ducts
1
1. Exhaust duct mounting screws, qty. 2
2. Alternator duct mounting screws, qty. 3
Figure 7-38 Alternator Air Inlet Duct, 20RESB and 20RESD
TP-6805 8/15
Alternator Duct Detail
2
24. Press the OFF button on the generator set
controller.
Connecting the battery and the battery charger.
Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and
negative to negative, to avoid electrical shock and damage to
the battery charger and battery(ies).
electrician install the battery(ies).
25. Reconnect the generator set engine starting
battery, negative (--) lead last.
26. Reconnect the carburetor heater (if equipped) to
the 120VAC receptacle.
27. Reconnect the utility power to the generator set.
28. Reconnect output leads or load circuit cables at the
field-connection terminal block.
3
4
3. Alternator air inlet duct
4. Exhaust duct
Section 7 Disassembly/Reassembly
Have a qualified
GM51561C
143