Status Message
Load Shed 1 Status Info
Load Shed 2 Status Info
Load Shed 3 Status Info
Load Shed 4 Status Info
Load Shed 5 Status Info
Load Shed 6 Status Info
* Programmable Interface Module (PIM) required.
] A load management device is an LCM, load shed kit, or RXT combined interface/ load management board.
[ Load management device required.
Figure 5-15 Status Messages Displayed on the RDC2 Controller
Generator Set State
Generator Management Off
ProtectiveRelayTrippedContactor
Synchronizing
Unloading
Figure 5-16 Generator Set States Related to Paralleling
TP-6805 8/15
Action
Notice
The digital output for LoadPriority1Shed
[
is active (contacts closed), indicating the
1st priority load shed has been activated.
Notice
The digital output for LoadPriority2Shed
[
is active (contacts closed), indicating the
2nd priority load shed has been
activated.
Notice
The digital output for LoadPriority3Shed
[
is active (contacts closed), indicating the
3rd priority load shed has been activated.
Notice
The digital output for LoadPriority4Shed
[
is active (contacts closed), indicating the
4th priority load shed has been activated.
Notice
The digital output for LoadPriority5Shed
[
is active (contacts closed), indicating the
5th priority load shed has been activated.
Notice
The digital output for LoadPriority6Shed
[
is active (contacts closed), indicating the
6th priority load shed has been activated.
Description
This generator has been stopped by generator management because it is not
presently needed to supply the load. The generator is available and will start if it is
needed again.
The contactor has been forced to open to protect one of the generators or the
customer's load.
The generator is actively trying to match frequency, voltage and phase with that of the
paralleling bus.
The generator is actively trying to transfer load from itself to the other generator.
Description/ Comments