Advertisement

Status Message
Gen Running
Low Fuel *
Minor Fault
NormSrcUnavl (RXT required)
OB1 CommLoss (option board)
OB2 CommLoss (option board)
OB3 CommLoss (option board)
OB4 CommLoss (option board)
Rmt StartCmd
(Remote Start Command
Issued)
Run Btn Ack
(Run Button Acknowledged)
Start Delay
(Engine Start Delay Active)
System Ready
VSpdStartCmd
(Variable Speed Start
Command)
* Programmable Interface Module (PIM) required.
] A load management device is an LCM, load shed kit, or RXT combined interface/ load management board.
[ Load management device required.
78
Section 5 Troubleshooting
Action
Description/ Comments
Notice
The digital output for Generator Running
(PIM) is active (contacts closed),
indicating the generator is running.
Notice
The digital output for Low Fuel (PIM) is
active (contacts closed), indicating any of
the digital inputs for Low Fuel Pressure
Warning, Low Fuel Level Warning or Low
Fuel Level Shutdown (PIM) is active
(low).
Notice
The digital output for Minor Fault (PIM) is
active (contacts closed), indicating either
the digital input for Ground Fault
Indicator Warning (PIM) is active (low) or
the controller detected Low Cranking
Voltage.
Notice
The normal power source (source1) is
disconnected, unavailable or
unacceptable.
Notice
Communication with option board #1 has
been lost.
Notice
Communication with option board #2 has
been lost.
Notice
Communication with option board #3 has
been lost.
Notice
Communication with option board #4 has
been lost.
Notice
The controller has received a remote
start signal while the master switch is in
AUTO, and will go to normal running.
Notice
The RUN button on the controller has
been pushed.
Notice
The digital output for Engine Start Delay
(PIM) is active (contacts closed),
indicating the engine is in between active
cranking cycles.
Notice
The digital output for System Ready
(PIM) is active (contacts closed),
indicating the generator has no active
faults or warnings.
Notice
A diagnostic exercise request has been
received by the controller.
Check
Check controller front panel
buttons for potential RUN
command. If in AUTO, check
remote start lines. Consult
ATS operation manual for
events that may cause the
generator to start.
Check customer equipment
connected to the PIM module.
Check customer equipment
connected to the PIM module.
Check cranking battery
condition.
Check for utility source power
outage. Check wiring and
connections to the ATS.
Check RBUS wiring to
inoperative option board.
(PIM, RXT, or load mgmnt
device)
]
Check RBUS wiring to
inoperative option board.
(PIM, RXT, or load mgmnt
device)
]
Check RBUS wiring to
inoperative option board.
(PIM, RXT, or load mgmnt
device)
]
Check RBUS wiring to
inoperative option board.
(PIM, RXT, or load mgmnt
device)
]
Verify remote start signal.
Consult ATS operations
manual for cause of generator
start.
Check for a remote exercise
command from OnCue.
TP-6805 8/15