Kohler 14RESA Manual page 55

Residential/commercial generator sets
Hide thumbs Also See for 14RESA:
Table of Contents

Advertisement

1. Adapter harness GM92802
2. Fuse connection
3. Run relay. Install near start relay. Install fuse (not shown) near relay.
Figure 4-12 Relay and Adapter Harness (for replacing original controller with revised controller only)
1. Mini circuit breaker
2. Cable tie
Figure 4-13 Mini Circuit Breaker (for replacing
original controller with revised controller
only)
TP-6805 8/15
1
#
GM92803
1
2
141329
2
GM93317
15. Check the firmware version on the controller. See
Section 4.5. Use SiteTech or the USB utility with a
laptop computer connected to the controller's USB
port to update the firmware to the latest released
version. See the SiteTech Software Operation
Manual or the USB Utility instruction sheet for
instructions.
16. Set up the controller as instructed in Section 4.7,
Controller Setup.
17. Calibrate the voltage. See Section 4.8, Voltage
Calibration.
18. If OnCuer Plus is used to monitor this generator
set, reset the OnCue password on the controller
and note the new password. See Section 4.9,
Setting the OnCue Password. Then connect with
OnCue Plus and enter the new password.
19. Verify that OnCuer Plus can communicate with the
generator set over the Internet before leaving the
job site.