6.14 Continuity Checks
WARNING
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Short circuits.
Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
To further check generator set components, disconnect
the battery and remove wiring harness plugs from the
Component
P1 wiring harness
Controller wiring
Auxiliary winding
breaker (20-amps)
Low oil pressure (LOP)
switch *
Temperature sensor
(OTS) *
* See Section 6.10.2, Fault Shutdown Switches
Figure 6-41 Continuity Checks
124
Section 6 Component Testing and Adjustment
Moving parts.
Do not contact electrical
Ohmmeter
Connections
P1-2 and ground
P2-6 and P2-7 (stator
leads 11 and 44)
P2-3 and P2-4 (stator
leads 55 and 66)
P1-1 and battery positive
(+)
55F (P2-3) and stator
lead 55
Lead 13 and ground
(engine block)
69R and 69 (P1-9 and
P1-10)
controller circuit board. Use an ohmmeter to check the
continuity of the components listed in Figure 6-41. Also
see Section 8, Wiring Diagrams.
Figure 6-41 gives resistance readings for functional
components. A zero reading on the ohmmeter indicates
continuity. No ohmmeter reading indicates very high
resistance or an open circuit. A measurement that
varies significantly from the value shown in the table
indicates
a
components.
Note: Disconnect the generator set battery before
performing continuity checks to prevent damage
to the ohmmeter.
For rotor and stator resistance and continuity checks,
see Section 6.3, Stator, and Section 6.4, Main Field
(Rotor).
Ohmmeter
Generator Set
Scale
State
R x 1
OFF
R x 1
OFF
R x 1
OFF
R x 100
OFF
R x 100
OFF
R x 100
OFF
R x 1000
OFF
faulty
component;
replace
Ohmmeter Readings for
Operative Components
Less than 1 ohm (continuity)
Any other reading indicates a poor
ground connection.
Less than 1 ohm (continuity). If no
continuity, check wiring.
Less than 1 ohm (continuity). If no
continuity, check wiring.
Less than 1 ohm (continuity). If no
continuity is found, check wiring.
Less than 1 ohm (continuity). If no
continuity is found, check for an open
circuit.
Less than 1 ohm (continuity). No
continuity indicates a faulty switch
and/or wiring.
180--2500 ohms, depending on
engine temperature. See
Section 6.10.2. Less than 1 ohm or
an open circuit indicates faulty wiring
or a faulty sensor.
faulty
TP-6805 8/15