Kohler 14RESA Manual page 59

Residential/commercial generator sets
Hide thumbs Also See for 14RESA:
Table of Contents

Advertisement

Generator ---->
Metering
Three-phase
Volts L1--L2:
Volts L2--L3:
Volts L3--L1:
Frequency:
Note: Pressing select when Reset Calibration: Yes is displayed will discard
the changes and reset the calibration to the original settings.
Figure 4-18 Voltage Calibration
TP-6805 8/15
Calibrate
240 V
Calibrate
240 V
Calibrate
240 V
60.0 Hz
Single-phase
Volts:
240V
Frequency:
60.0 Hz
Reset
Calibration
<---- Return
Calibrate
To Calibrate Voltage:
1. Press Select when the voltage is
displayed. The voltage flashes.
2. Press the Up or Down arrow
button to change the setting.
3. Press the Select button to save the
setting.
4. Press the down arrow button to
move to the next menu.
Reset
Calibration? No
Reset
Calibration? Yes
Section 4 Controller
tp6811
59