SiteTech Group
Generator Protection
Digital Input A1
Digital Input A2
Digital Input B1
Digital Input B2
Digital Output A1
Digital Output A2
Digital Output B1
* Read Only = Not adjustable
[ Notes indicate applicability to genset model and accessories. N/A = Not applicable to these generator sets.
] See TT-1584 for more information about digital inputs and outputs.
w Load management device (LCM, load shed kit, or RXT with combined interface/ load management board)
46
Section 4 Controller
Parameter
Loss Of AC Sensing Shutdown
Delay
Genset Low Voltage Shutdown
Delay
Genset High Voltage Shutdown
Delay
Genset Low Voltage Shutdown
Limit
Genset High Voltage Shutdown
Limit
Genset Short Term Low
Frequency Shutdown Delay
Genset Long Term Low
Frequency Shutdown Delay
Genset High Frequency
Shutdown Delay
Genset Low Frequency
Shutdown Limit
Genset High Frequency
Shutdown Limit
Digital Input A1 Value
Digital Input A1 Enabled
Digital Input A1 Event
Digital Input A2 Value
Digital Input A2 Enabled
Digital Input A2 Event
Digital Input B1 Value
Digital Input B1 Enabled
Digital Input B1 Event
Digital Input B2 Value
Digital Input B2 Enabled
Digital Input B2 Event
Digital Output A1 Value
Digital Output A1 Event
Digital Output A2 Value
Digital Output A2 Event
Digital Output B1 Value
Digital Output B1 Event
Adjustment
Range *
Units
s
Read Only
s
Read Only
s
Read Only
%
Read Only
%
Read Only
s
Read Only
s
Read Only
s
Read Only
%
Read Only
%
Read Only
Read Only
True or False
See dropdown list in
SiteTech.
]
Read Only
True or False
See dropdown list in
SiteTech.
]
Read Only
True or False
See dropdown list in
SiteTech.
]
Read Only
True or False
See dropdown list in
SiteTech.
]
Read Only
See dropdown list in
SiteTech.
]
Read Only
See dropdown list in
SiteTech.
]
Read Only
See dropdown list in
SiteTech.
]
Default
Setting
Notes
[
3
10
2
80
120
10
60
10
90
110
False
N/A
True
N/A
Fuel
N/A
Pressure
Low
Warning
False
N/A
True
N/A
Auxiliary
N/A
Input
Warning
False
PIM
False
None (0)
False
PIM
False
None (0)
False
N/A
NFPA 110
N/A
Alarm
Active
N/A
N/A
N/A
N/A
PIM
False
Generator
Running
TP-6805 8/15