Pentair PROSTOP-E Installation And Operation Manual page 24

Table of Contents

Advertisement

CONTROL OVERVIEW
CHANNEL SETUP - ALARMS
1
2
3
4
5
1.
Rate Alarm Threshold
Adjusts threshold value for the Rate Alarm - can be set
from 10-30%. This value is the percentage of difference
between the actual rate of application and the intended
(target) rate. Default setting is 10%.
2.
Low Pressure Alarm
Enables and adjusts value for Pressure Alarm - set value
to notify operator when low level is reached. Range: 0 to
50% of FULL SCALE setting.
3.
High Pressure Alarm
Enables and adjusts value for Pressure Alarm - set value
to notify operator when high level is reached. This can be
set to OFF (0) or up to 100% of FULL SCALE setting.
4.
Tank Alarm Level
This enables and specifies a value for the Tank Alarm.
When enabled, the approximate value can be seen on the
tank gauge display on the Home screen as a red line.
5.
Nozzle Check Alarm (hybrid mode only)
This enables and specifies a value for the Nozzle
Check Alarm. In hybrid mode, the flowmeter is used for
accumulating counters and as a check against worn
nozzles. When enabled, if the actual flow differs from the
calculated flow from pressure by a defined percentage,
an alarm will notify the operator.
24
HYP1100 (04-08-21)