CONTROL OVERVIEW

CHANNEL SETUP - OPERATION
SET PWM LIMITS
This setup routine establishes low and high PWM duty cycle
limits for a PWM controlled device.
3
5
PROCEDURE:
SET MINIMUM LIMIT
1.
With at least one section turned on, press the Run/Hold
softkey.
2.
Press the Increase button until the pump shows steady
minimum Rate/Min. Data window on the right shows real-
time duty cycle.
3.
To save this value as the new minimum duty cycle %,
press the Minimum button onscreen.
SET MAXIMUM LIMIT
4.
Press the Increase button until maximum Rate/Min. is
reached. Data window on the right shows real-time duty
cycle %.
5.
To save this value as the new maximum duty cycle %,
press the Maximum button onscreen.
32
SAVE CHANGES, AND EXIT
6.
Press Run/Hold softkey to stop pump.
7
7.
Press Confirm softkey to save changes and exit back to
Channel Setup.