NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Menu
System
Setting
s
Issue 04 (2021-03-15)
Parameter
Description
Cold aisle
This parameter can
temperature
be enabled only
and humidity
when at least two
sharing
smart cooling
products in the group
are equipped with
cold aisle T/H
sensors. When this
parameter is enabled,
the smart cooling
product, which is not
configured with the
cold aisle T/H sensor
in the group, is
logically controlled by
using the acquired
value of the
configured cold aisle
T/H sensor.
Hot aisle
This parameter can
temperature
be enabled only
and humidity
when at least two
sharing
smart cooling
products in the group
are equipped with
hot aisle T/H sensors.
When this parameter
is enabled, the smart
cooling product,
which is not
configured with the
hot aisle T/H sensor
in the group, is
logically controlled by
using the acquired
value of the
configured hot aisle
T/H sensor.
Dual power
Primary power first
supply setting
or Primary power
only can be set as
required.
Altitude
Set the parameter
according to the
actual situation.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
Disable
Disable
Retain the default value.
-