NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Figure 3-58 Connecting the FE teamwork network cable (NetCol5000-C030/C032)
Figure 3-59 Connecting FE teamwork network cables (multiple units)
----End
3.12.4.3.2 Connecting the CAN Teamwork Cable
Context
In CAN networking, one teamwork network supports a maximum of 32 smart
cooling products. If CAN networking is required onsite, set Teamwork CAN
resistor enable on the Teamwork settings page for the first and last smart
cooling products to Yes.
Procedure
Step 1 Prepare an 8-pin standard network cable. The following figure shows the wire
sequence requirements.
Issue 04 (2021-03-15)
Copyright © Huawei Technologies Co., Ltd.
3 Installation
74