NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Figure 3-36 Water pipe positions (NetCol5000-C065, top and bottom pipe
routing)
(1) Water inlet pipe
(3) Forcible drainpipe
3.8.2 Connecting a Drainpipe
The external drainpipe must have a certain gradient (> 1:100), and no
accumulated water is allowed.
Step 1 Clean the engineering pipe and remove the thermal insulation foam from the
drainpipe plug.
Step 2 Remove the drainpipe plug.
Step 3 Install a pipe adapter and seal it with sealant.
Step 4 (Rigid pipe connection) Connect the water pipe using a hot melt device and
connect the drainpipe to the external drainage system.
(Hose connection) Secure the hose using hose clamps and connect the drainpipe
to the external drainage system.
Step 5 Wrap thermal insulation foam around the pipe.
Figure 3-37 Connecting the automatic drainpipe (rigid pipe connection)
Issue 04 (2021-03-15)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
(2) Water outlet pipe
(4) Humidifier water inlet pipe
3 Installation
59