Huawei NetCol5000-C030 User Manual page 102

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Table 4-4 Parameter description
Parameter
Temperatur
e and
humidity
control type
Temperatur
e control
mode
Issue 04 (2021-03-15)
Description
Cold aisle, Hot aisle, Return
air, or Supply air can be set as
required. The temperature and
humidity set points correspond
to the selected control type can
be set.
This parameter controls the
temperature inside the room or
aisles based on the Average
value, Max value, or Min
value of the temperatures
collected by sensors.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
● When the application
scenario is cold or hot aisle
containment, you are
advised to choose Cold aisle
if the cold aisle T/H sensors
are configured, and choose
Supply air if the cold aisle
T/H sensors are not
configured.
● When the application
scenario is non-aisle
containment, you are
advised to choose Return
air, and choose Cold aisle if
the cold aisle T/H sensors
are configured.
● Hot aisle is not
recommended.
● Average value: Select
Average value if the
temperature is to be
controlled based on the
averaged value of the
temperatures collected by
multiple sensors.
● Max value: Select Max
value if the temperature is
to be controlled based on
the maximum value of the
temperatures collected by
multiple sensors.
● Min value: Select Min value
if the temperature is to be
controlled based on the
minimum value of the
temperatures collected by
multiple sensors.
94