Huawei NetCol5000-C030 User Manual page 106

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Paramete
r
Enable
teamwork
CAN
resistor
Teamwork
function
Networkin
g mode
Number
of systems
in this
group
Issue 04 (2021-03-15)
Description
Indicates the build-out
resistor status of each
smart cooling product in a
teamwork group. Set the
parameter if CAN network
is used.
Disable or enable the
teamwork function. If the
teamwork function is
disabled, this device is
operating according to its
own control. If the
teamwork function is
enabled, this device works
in harmony with others that
in the same group.
Networking mode for the
teamwork. The networking
mode set on the screen
must be consistent with the
actual networking mode.
Otherwise, the teamwork
control function will be
unavailable. If the
networking mode changes,
select the corresponding
networking mode on the
screen.
Number of the smart
cooling products in this
group (1 to 32 can be set).
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
● Set this parameter
to No for non-
teamwork
scenarios.
● For teamwork
scenarios, set this
parameter to Yes
for the first and
last smart cooling
products in a
teamwork group,
and set it to No for
other smart cooling
products.
Set this parameter
based on the onsite
device heat
distribution.
Networked over CAN
or MAC_CAN. CAN
network indicates
teamwork control
over a CAN bus,
MAC_CAN network
teamwork control
over an FE port.
If the device is
connected to the
smart ETH gateway or
ECC800, set the
parameter to
MAC_CAN network.
In other scenarios, set
the parameter to CAN
network.
Total number of the
smart cooling
products in this group.
Default
Value
No
Disable
CAN
network
3
98

Advertisement

Table of Contents
loading