Huawei NetCol5000-C030 User Manual page 109

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Paramete
r
Differentia
l pressure
sharing
Cold aisle
temperatu
re and
humidity
sharing
Hot aisle
temperatu
re and
humidity
sharing
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step 1
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
If the teamwork control succeeds, the teamwork topology of the smart cooling
product in the group is displayed, as shown in
note for the screen.
Issue 04 (2021-03-15)
Description
When this parameter is
enabled, the smart cooling
product, which is not
configured with the
differential pressure sensor
in the group, is logically
controlled by using the
acquired value of the
configured differential
pressure sensor.
This parameter can be
enabled only when at least
two smart cooling products
in the group are equipped
with cold aisle T/H sensors.
When this parameter is
enabled, the smart cooling
product, which is not
configured with the cold
aisle T/H sensor in the
group, is logically controlled
by using the acquired value
of the configured cold aisle
T/H sensor.
This parameter can be
enabled only when at least
two smart cooling products
in the group are equipped
with hot aisle T/H sensors.
When this parameter is
enabled, the smart cooling
product, which is not
configured with the hot
aisle T/H sensor in the
group, is logically controlled
by using the acquired value
of the configured hot aisle
T/H sensor.
and
Step
2.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
This parameter can be
enabled when there
are at least two smart
cooling products in
the group are
configured with
differential pressure
sensors.
This parameter can be
enabled when there
are at least two smart
cooling products in
the group are
configured with cold
aisle T/H sensors.
This parameter can be
enabled when there
are at least two smart
cooling products in
the group are
configured with hot
aisle T/H sensors.
Figure
4-7.
Table 4-7
Default
Value
Disable
Disable
Disable
.
describes the
101