Figure 3-6 Connecting a humidifier water inlet pipe
(1) Connector with outer screw
threads: G 3/4 inch

3.1.2.4 Chilled Water Inlet and Outlet Pipes

The following illustrates how to connect water inlet and outlet pipes to reserved
ports on the cabinet.
Figure 3-7 Connecting the water inlet and outlet pipes
(1) NetCol5000-C065: G 1–1/2 in. port with
inner threads (reserved device port)
NetCol5000-C030/C032: G 1 in. port with inner
threads (reserved device port)
Issue 04 (2021-03-15)
NO TE
The object shown in the dotted line box is the water inlet pipe connector with outer screw
threads delivered with smart cooling products. Other parts are not provided and need to be
purchased.
Copyright © Huawei Technologies Co., Ltd.
(2) Adapter with inner screw
threads: G 3/4 inch. Plastic
materials such as PA66 and
metal materials are
recommended.
(2) NetCol5000-C065: Seamless steel pipe with
a G 1–1/2 in. external threaded connector
(engineering purchase)
NetCol5000-C030/C032: Seamless steel pipe
with a G 1 in. external threaded connector
(engineering purchase)
3 Installation
(3) Matched with the adapter,
the pressure resistance should
be at least 0.7 MPa
37