Huawei NetCol5000-C030 User Manual page 107

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C030:
Table of Contents

Advertisement

NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Paramete
r
Number
of running
systems in
this group
Rotation
function
Rotation
period
Rotation
time
Forced
rotation
Issue 04 (2021-03-15)
Description
Number of active units in a
group. The value ranges
from 1 to Number of air
conditioners in this group.
Disable or enable the active
and standby smart cooling
products to change identity
after a certain time,
maximizing their service
life.
Rotation days (1–30).
24 hours in a day (0–23).
Forced rotation specifies
whether to enable a
forcible rotation on the
group before the specified
rotation time. After a forced
rotation, the accumulated
time is recalculated.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Rule
The master unit
assigns running units
in ascending order of
the addresses. The
address should be in
the range of 1–32. The
remaining units are
automatically
classified as standby
devices.
This function is
recommended when
the heat is even.
7 by default
0 by default
This item is set to No
by default. If forced
rotation is required,
the function is set to
Yes.
Default
Value
2
Disable
7 day (s)
0
No
99