NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Step 4 Add an SNMPv3 user.
1.
2.
3.
Issue 04 (2021-03-15)
Figure 4-10 Setting the write community
Tap Add under SNMP V3.
Enter a planned value for User Name, select values for Auth Protocol and
Prop Protocol from drop-down list boxes, and tap
4-11.
MD5 and DES protocols are not secure. It is recommended that you set Auth
Protocol to SHA, and set Prop Protocol to AES. The following operations use
the recommended settings as an example.
Figure 4-11 Setting the protocol type
NO TICE
Passwords of an authentication protocol and proprietary protocol must
comply with the following policies:
– The password must consist of 8–15 characters and contain at least two
types of characters among uppercase letters (A–Z), lowercase letters (a–z),
and digits (0–9).
– A password must be different from the corresponding user name or
inverted user name.
– A password must not be a string containing duplicate sections, such as
12a12a12a.
Set SHA Password and Confirm Password as planned, and tap
shown in
Figure
4-12.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
, as shown in
Figure
, as
107