NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
(3) Direct connection of external teeth
(engineering purchase)
(5) Nut
3.1.2.5 Pipe Support
Supports for pipes and water pipes as shown in the figure. The actual appearance
of the supports will be different based on onsite situations.
Figure 3-8 Pipe supports (unit: mm)
3.1.2.6 Cables
The following lists the cables and devices to be connected. When connecting
cables, fit them with protective hoses.
Issue 04 (2021-03-15)
NO TE
● The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including
the thermal insulation foam).
● Install a support every 2500 mm for the straight sections of pipes, and 1000 mm away
from each bending point in turning sections.
Copyright © Huawei Technologies Co., Ltd.
(4) Sealing ring
(6) NetCol5000-C065: Aluminum plastic pipe
with an inner diameter of 41 mm (engineering
purchase)
NetCol5000-C030/C032: Aluminum plastic pipe
with an inner diameter of 26 mm (engineering
purchase)
3 Installation
38