NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Item
Water
supply
requirem
ents of
wet film
Power
distributi
on
Operating Specifications
Table 2-4 Operating specifications
Item
Operating ambient
temperature
Operating ambient
humidity
Inlet water
temperature of
chilled water or
glycol solution
Storage temperature
Storage humidity
Altitude
Temperature
adjustment range
Temperature
adjustment precision
Humidity adjustment
range
Issue 04 (2021-03-15)
NetCol5000-C065
The inlet water pressure should be in the range of 0.1–0.7 MPa (A
reducing valve must be installed if the inlet water pressure exceeds
0.7 MPa.), and the temperature should be in the range of 1°C–40°C.
The wet film humidifier should use tap water (no water treatment
facility needed for the inlet water) that meets the following
requirements:
● Non-freezing and nephelometric turbidity units (NTU): < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO
Leakage circuit breakers are not used for the main power route. If
leakage circuit breakers are required by the customer or by local
regulations, use the residual current circuit breakers (RCCBs) that
are not sensitive to the single-phase DC pulses and transient current
pulses.
NetCol5000-C065
4–55°C
5%–95% RH
7–19°C (water, glycol solution)
–40°C to +70°C
5%–95% RH (non-condensing)
0–1000 m: normal use; 1000–4000 m: derated
15–35°C
±1°C
20%–80% RH