NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
Place the sheet metal of the water sensor upwards and its detection board
downwards on the ground.
----End
3.12.6 Connecting the T/H Sensor Outside the Cabinet
Context
T/H sensors outside the cabinet are configured to detect the temperatures of
cold/hot aisles. They can be flexibly installed on the server cabinet based on onsite
situation. It is recommended that the T/H sensors be deployed near heat sources
in the hot aisle, or in places which lacks cooling air in the cold aisle. The T/H
sensors outside the cabinet must be near the smart cooling product to sense the
temperature of the outlet air, and must be away from the air exhaust vents of
other smart cooling products
Procedure
Step 1 Connect the T/H sensors outside the cabinet and the T/H sensors at the air return
side in series.
Figure 3-67 Connecting T/H sensors in series
Figure 3-68 Cables routed outside the cabinet (NetCol5000-C065)