Table 4-17 Battery Setting
Item
Bat mode
shut
Backup time
warning
Remain. cap.
warning
Thres. of low
batt. SOC
over dry
contact (%)
Thres. of low
batt. volt.
over dry
contact (V/
cell)

4.2.2.2 Comm. Config. Page

Open the Comm. Config. page to set communications information.
Figure 4-40 Comm. Config.

4.2.2.3 Control Page

Open the Control page to control the system running.
Issue 01 (2021-04-14)
Description
In battery mode, the UPS can
automatically power off according to the
preset shutdown delay time. If the
parameter is disabled, this function is not
available.
An alarm is generated if this parameter is
set to Enable and the backup time is less
than the warning threshold.
An alarm is generated if this parameter is
set to Enable and the remaining capacity
is less than the warning threshold.
If an output dry contact is set to Low
battery SOC, and the battery SOC is lower
than this threshold, the output dry
contact will output signals.
If an output dry contact is set to Batt.
Volt. Below Threshold, and the battery
voltage is lower than this threshold, the
output dry contact will output signals.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default
Value
Value
Range
Disable
Disable,
Enable
Disable
Disable,
Enable
Disable
Disable,
Enable
75
5–80
2.8
2.60–
3.20
106