Huawei UPS5000-S-600 kVA User Manual page 167

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0356
Battery Mode
0359
No power
supplied
0332
Output disabled
0337
PDC bypass input
breaker open
0338
PDC output
breaker open
0341
PDC Maint.
breaker closed
0342
Mains input
breaker open
0343
BPM input
breaker open
0340
Maint. breaker
closed
0335
Generator
connected
Issue 01 (2021-04-14)
Severity
Cause
Minor
The UPS is
working in battery
mode.
Warning
No power is
supplied.
Minor
The output is
disabled.
Critical
The bypass input
circuit breaker on
the PDC is OFF.
Critical
The output circuit
breaker on the
PDC is OFF.
Minor
The maintenance
circuit breaker on
the PDC is ON.
Critical
The mains input
circuit breaker is
OFF.
Critical
The bypass input
circuit breaker is
OFF.
Minor
The maintenance
circuit breaker is
ON.
Warning
The generator is
connected.
Copyright © Huawei Technologies Co., Ltd.
A Alarm List
Solution
The running status is
displayed. See details about
how to handle other alarms.
The running status is
displayed. See details about
how to handle other alarms.
The running status is
displayed. See details about
how to handle other alarms.
The running status is
displayed. No further
measures are required.
1. Check that all UPS output
circuit breakers are ON.
2. On the LCD, check that
PDC output breaker open
alarm has disappeared. If
the alarm persists, tap the
Clear Fault button to clear
the alarm.
The running status is
displayed. No further
measures are required.
The running status is
displayed. No further
measures are required.
The running status is
displayed. No further
measures are required.
The running status is
displayed. No further
measures are required.
The running status is
displayed. No further
measures are required.
159