Huawei UPS5000-S-600 kVA User Manual page 96

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Item
Battery type
Battery
capacity (Ah)
Maintenance
period (d)
EOD restart
EOD restart
delay (min)
Sched.
shallow dis.
test
Sched.
shallow dis.
test time
Issue 01 (2021-04-14)
Description
Type of batteries connected
to the UPS.
When the UPS is connected
to the SmartLi, the battery
type is automatically
identified as lithium battery.
Capacity of lithium batteries
connected to the UPS (the
value is automatically
obtained).
Specifies the interval for
reminding users of battery
maintenance.
If this parameter is set to 0,
there is no reminder.
If the mains is not
functioning normally, the
UPS will transfer to battery
mode. When batteries reach
the EOD threshold, the
bypass is disabled, and EOD
restart is Enable, the UPS
will restart as soon as the
mains resumes.
If EOD restart is disabled,
clear the alarm manually or
enable the restart function
for the UPS.
If EOD restart is set to
Enable, the UPS starts
working after the time set for
EOD restart delay when the
input recovers from the
power failure upon EOD.
When certain conditions are
met, the charger shuts down,
and batteries supply power
to loads. The system records
the battery discharge data as
the reference for battery
capacity and lifespan.
Time for scheduled shallow
discharge test.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
VRLA batt.
VRLA batt.,
lithium batt.
-
-
0
0–365
Enable
Disable,
Enable
10
1–1440
Disable
Disable,
Enable
00:00 - 06:00
00:00 - 06:00,
06:00 - 12:00,
12:00 - 18:00,
18:00 - 24:00
88