Huawei UPS5000-S-600 kVA User Manual page 98

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Item
MUE05A connection
Batter ground fault [BTG]
D.G. connection [GEN]
BCB connection [OL]
Battery breaker [STA]
PDC output breaker [OUT]
PDC maintenance breaker
[MT]
BP/SYSMT Switch
BP/SYSMT switch function
SPD/SYSOUT Switch
SPD/SYSOUT switch function
MUE06A connection
MUS05A DO_1 Action,
MUS05A DO_2 Action,
MUS05A DO_3 Action,
MUS05A DO_4 Action
Issue 01 (2021-04-14)
Copyright © Huawei Technologies Co., Ltd.
Description
Specifies the MUE05A connection status.
Independent input signals can be enabled only
when this parameter is set to Enable.
Enable or disable battery grounding fault
detection.
Enable or disable D.G. connection detection.
Enable or disable BCB connection detection.
Enable or disable battery circuit breaker status
detection.
Enable or disable PDC output circuit breaker
status detection.
Enable or disable PDC maintenance circuit
breaker status detection.
If the BP/SYSMT switch is set to Enable, the
port has dry contact signal access. Using the
port depends on the status of the BP/SYSMT
switch.
If the BP/SYSMT switch is set to Enable, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is
used to detect the status of the PDU bypass
input switch, or system maintenance switch.
If the SPD/SYSOUT switch is set to Enable, the
port has dry contact signal access. How a user
uses the port depends on the status of the SPD/
SYSOUT switch.
If the SPD/SYSOUT switch is set to Enable, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is
used to detect the status of the PDU input surge
protector, or system output switch.
Specifies the MUE06A connection status. If this
parameter is set to Enable, the mains and
bypass backfeed protection is enabled.
Controls the status of DO ports on the MUS05A
dry contact card.
4 User Interface
90

Advertisement

Table of Contents
loading

Table of Contents