Huawei UPS5000-S-600 kVA User Manual page 53

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
● The UPS can generate large leakage currents. A circuit breaker that provides
● If multiple UPSs are to be connected in parallel, input and output power cables
The currents listed in the following table are measured at a rated voltage of 380 V.
Table 3-2 Recommended power cable cross-sectional area
Item
Mains input
connector
Bypass input
connector
Output connector
Battery input
connector
Issue 01 (2021-04-14)
NO TICE
leakage current protection is not recommended.
for each UPS should have the same length and specifications.
Mains input current (A)
Recommended cross-
2
sectional area (mm
Bypass input current (A)
Recommended cross-
2
sectional area (mm
Output current (A)
Recommended cross-
2
sectional area (mm
Nominal battery discharge current (A) 1316
Maximum battery discharge current
(A)
Recommended cross-
2
sectional area (mm
When selecting, connecting, and routing power cables, follow local safety
regulations and rules.
Copyright © Huawei Technologies Co., Ltd.
L1
)
L2
L3
PE
L1
)
L2
L3
PE
U
)
V
W
PE
+
)
-
PE
Specifications
1055
4 x (3 x 185 + 1 x 95)
912
4 x (3 x 185 + 1 x 95)
912
4 x (3 x 185 + 1 x 95)
1576
3 x (2 x 240)
240
3 Installation
45