Huawei UPS5000-S-600 kVA User Manual page 163

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0043-1
Fan abnormal
0043-2
0043-3
0043-4
0047-1
Not ready
0060-4
Inverter
abnormal
0061-2
Inverter alarm
Issue 01 (2021-04-14)
Severity
Cause
Critical
● The fan for the
● The fan
The fan is faulty.
● The fan is
● The fan
Critical
The ready switch
is OFF.
Critical
● A load short-
● A short circuit
Minor
● The I2C bus is
● The E2PROM is
Copyright © Huawei Technologies Co., Ltd.
Solution
Replace the faulty power
power module
module.
is abnormal.
monitoring
cable for the
power module
is not working
properly.
Check the fan or replace the
bypass module.
1. Replace the fan.
faulty.
2. Check the fan monitoring
monitoring
cable is faulty.
Close the ready switch.
1. Check load cable
circuit occurs.
2. If load cable distributions
occurs inside
the module.
(This fault
seldom
occurs.)
1. Rectify the fault and check
not normal.
faulty.
2. If the alarm is generated
A Alarm List
cable.
distributions.
are normal, replace the
power module.
whether the alarm is
cleared.
again, replace the power
module.
155