Huawei UPS5000-S-600 kVA User Manual page 66

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Figure 3-17 Connecting battery cables
Step 10 Route signal cables. Bind cables to the cabinet.
1.
2.
3.
● Bind signal cables and power cables separately.
● The number and colors of signal cables are for reference only.
● The figure uses the cable connection between the UPS and the SmartLi as an
Issue 01 (2021-04-14)
Connect the COM port on the monitoring interface unit in the master SmartLi
cabinet to the COM2 port on the monitoring interface card.
(Optional) Connect the network port on a PC to the FE port of the monitoring
interface card.
(Optional) Connect the external network management device to the RS485
port of the monitoring interface card.
NO TICE
example.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
58