UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Silk Screen
BSC
Table 2-5 Indicator description
Indicator
NORMAL
ALM
FAULT
Functions
Issue 01 (2021-04-14)
Description
The BSC port is used in a dual-bus system to synchronize
output frequencies and phases between UPS systems, ensuring
that two buses can switch with each other.
BSC cables are hot-swappable.
NO TE
For a single UPS, the parallel cable is not needed.
Color
Green
Yellow
Red
As a control interface for the entire system, the ECM communicates with each
module and provides a bus to communicate with the dry contact card. The
ECM ensures equalized output currents between modules so that load power
is equally shared.
Provides module running information for the MDU.
Controls the running of a single UPS5000 and a parallel system, and reports
the UPS5000 status information to other monitoring modules.
The system provides three types of CAN communication: monitoring CAN
communication, intra-rack parallel CAN communication, and inter-rack
parallel CAN communication.
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
This ECM is the active ECM.
Blinking at
This ECM is the standby ECM and it is
0.5 Hz
ready.
Off
This ECM is not ready or the CPLD of this
ECM is being upgraded.
Blinking at
The DSP of the ECM is being upgraded or
4 Hz
not configured.
Steady on
The ECM has a minor alarm, but it does
not need to be replaced.
Off
The ECM has no minor alarm or the DSP
of the ECM is being upgraded.
Steady on
The ECM has a critical alarm.
Off
The ECM has no critical alarm or the DSP
of the ECM is being upgraded.
2 Overview
28