Huawei UPS5000-S-600 kVA User Manual page 162

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0032-1
Battery
overvoltage
protection
0036-2
Battery
maintenance
reminder
0037-1
Battery
undervoltage
0040-7
Rectifier
abnormal
Issue 01 (2021-04-14)
Severity
Cause
Critical
● The battery
● The configured
● The actual
Warning
The time for
maintenance
arrives.
Critical
● The UPS has
● The charger is
Critical
● The fan for the
● The air channel
Copyright © Huawei Technologies Co., Ltd.
Solution
1. Check the battery voltage.
voltage is
2. Check that the configured
greater than
the upper
threshold.
3. Check that the actual
number of
batteries is less
than the actual
number.
number of
batteries does
not meet
requirements.
Maintain the batteries.
1. Check whether the battery
worked in
battery mode
2. Check whether the output
for an
extended
3. Check whether any battery
amount of
time.
4. Check whether any battery
faulty.
1. Check that the air channel
power module
is not
functioning
2. Check whether the fans
properly.
for the power
module is
obstructed.
A Alarm List
number of batteries
matches the actual
number.
number of batteries meets
requirements.
voltage is normal.
is overloaded.
is damaged. If yes, replace
the battery.
charger generates an
alarm. If yes, replace the
faulty module.
for the module is free from
blockage.
are functioning properly.
Replace the power module
if the fans are faulty.
154