Huawei UPS5000-S-600 kVA User Manual page 94

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Bypass Settings
Figure 4-24 Bypass Settings
Item
Maximum
bypass
voltage
Issue 01 (2021-04-14)
Description
When the difference between
the bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
● When the
voltage level is
380 V, the
default value is
+15%.
● When the
voltage level is
400 V, the
default value is
+15%.
● When the
voltage level is
415 V, the
default value is
+10%.
● When the
voltage level is
420 V, the
default value is
+10%.
● When the
voltage level is
480 V, the
default value is
+10%.
Value
Range
+10%,
+15%,
+20%,
+25%
86