Huawei UPS5000-S-600 kVA User Manual page 134

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Set system parameters with caution because the settings determine normal UPS
operation.
● Set Single/Parallel after double check. Incorrect setting may affect the normal
● Output voltage level refers to the line voltage level. Set it based on site
● Set Output frequency correctly; otherwise, loads may be affected and the UPS
Figure 5-1 Settings Wizard
Step 2 (Optional) On the LCD of the system, choose System Info > Settings > DST
Settings and set the DST mode as required.
Step 3 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. If there is
any other alarm, you need to rectify the fault.
Issue 01 (2021-04-14)
NO TICE
UPS operation.
requirements.
may not work properly.
NO TE
● Set the time and date correctly. Incorrect time and date will cause false fault analysis
during maintenance or repair.
● After you set network parameters, connect the UPS to the network over a network
cable, which enables you to remotely manage the UPS. If you do not need remote
management, retain the default network parameter settings.
Copyright © Huawei Technologies Co., Ltd.
5 Operations
126