Huawei UPS5000-S-600 kVA User Manual page 104

Singapore, threephase, three-wire
Hide thumbs Also See for UPS5000-S-600 kVA:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Singapore, Three-phase, Three-wire)
Screen Calib. Menu
Figure 4-33 Screen Calib. screen
Wizard Startup
The wizard startup can be used to test the bypass, mains inverter, inverter/bypass
switch, battery inverter, battery charging capability, battery switch tripping and so
on.
Perform operations as prompted.
Before starting the wizard, ensure that:
● The system is a single UPS system.
● No minor or critical alarm occurs.
● The UPS works in normal mode with a load ratio fluctuation less than 10%.
● The UPS generates no battery overtemperature, overvoltage, or overcurrent
● The mains, batteries, charger, and discharger are normal. No overload alarm is
● SOC > 30%
Issue 01 (2021-04-14)
NO TICE
alarm. No generator is connected to the UPS.
generated.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
96